202
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix B
CGCM-DLR Unit Math Models
Soft Start Control
The soft start control function is provided to cause orderly build-up of terminal
voltage from the residual voltage to the rated voltage in desired time with
minimal overshoot. In CGCM-DLR units, the fast dynamic response is used
while the voltage reference is adjusted based on the elapsed time. When the
system is under start-up condition, the voltage reference is adjusted by the
amount calculated based on two programmable parameters, initial soft-start
voltage level (V
O
), and desired time (T
SS
) to build up to the rated voltage. Its
mathematical model is shown in Soft Start Control. The soft start gain (K
SS
) is
calculated by using this formula.
K
SS
= (V
REF
- V
O
) / T
SS
Figure 68 - Soft Start Control
Time From Start
AVR
Summing
Point
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......