Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
171
Troubleshooting
Chapter
7
Table 29 - Synchronizing
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
No close indication from CGCM-DLR
unit
Phase not matched
Observe Phase match tag during
synchronization
If phase match indicated, check
close command tag. If no phase
match indicated, check phase match
error
Observe phase error reported by
CGCM-DLR unit during
synchronization
If no phase error is reported, correct
wiring and verify appropriate
Synchronization mode is active
If phase error reported, verify that
governor is responding to reported
error
Close output from CGCM-DLR unit
not being examined
Monitor Close breaker tag from
CGCM-DLR unit
If close indication received, check
use of tag. If no close indication,
check match errors
Frequency not matched
Observe frequency match tag during
synchronization
If frequency match indicated, check
close command tag. If no frequency
match indicated, check frequency
match error
Observe frequency error, generator
frequency, and selected bus
frequency reported by CGCM-DLR
unit during synchronization
If no frequency error is reported,
correct wiring and verify that
appropriate Synchronization mode is
active
If frequency error reported, verify
that governor is responding to
reported error
Sync parameter configuration
incorrect
Observe configured synchronization
limits, VT input configuration, and
generator rated entries
Correct any errors in the
configuration entries
No close indication from CGCM-DLR
unit (cont.)
Voltage not matched
Observe voltage match tag during
synchronization
If voltage match indicated, check
close command tag. If no voltage
match indicated, check voltage
match error
Observe voltage error, generator
voltage, and selected bus voltage
reported by CGCM-DLR unit during
synchronization
If no voltage error is reported,
correct wiring and verify that
appropriate Synchronization mode is
active
If voltage error is reported, verify
voltage setpoint to CGCM-DLR unit
is being adjusted appropriately to
provide voltage correction
Close indication from CGCM-DLR
unit when sync parameters not met
Configuration errors
Observe VT and Bus offset
configuration parameters to verify
that they reflect the
desired/expected VT wiring
Correct configuration to match
expected VT wiring
Wiring errors
Adjust manually such that test
equipment (reference) indicates
synchronism, then observe
diagnostics above. This information
can be used to determine most
likely wiring error. Voltage not
matched, verify that PT wiring and
VT ratios are correct. Phase or
frequency not matched; verify phase
rotation and polarity of VT wiring
Correct VT wiring
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......