Line-drop Compensation Inputs to CGCM-DLR Unit
•
LineDropComp
- This tag configures the amount of voltage droop that is
experienced during paralleling generator applications.
Under-excitation Limit Inputs to CGCM-DLR Unit
•
UEL_En
- The setting of this tag enables the Under-excitation Limiting
function.
•
UEL_Kg
- This tag lets you adjust the proportional gain of the
Under-excitation limiter. It also determines the response of the limiter to
an Under-excitation event. An increase in this term increases the speed of
the response of the limiter.
•
UEL_Ki
- This tag lets you adjust coarse loop gain and overall gain of the
Under-excitation limiter. This tag determines the characteristic of the
dynamic response to an Under-excitation event.
•
UEL_Curve_W_Pt1
– This tag is used as the watt coordinate in the first
watt, VAR coordinate pair, that, in combination with four other watt, VAR
coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_W_Pt2
– This tag is used as the watt coordinate in the
second watt, VAR coordinate pair, that, in combination with four other
watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_W_Pt3
- This tag is used as the watt coordinate in the third
watt, VAR coordinate pair, that, in combination with four other watt, VAR
coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_W_Pt4
- This tag is used as the watt coordinate in the
fourth watt, VAR coordinate pair, that, in combination with four other
watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_W_Pt5
- This tag is used as the watt coordinate in the fifth
watt, VAR coordinate pair, that, in combination with four other watt, VAR
coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_VAR_Pt1
- This tag is used as the VAR coordinate in the
first watt, VAR coordinate pair, that, in combination with four other watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_VAR_Pt2
- This tag is used as the VAR coordinate in the
second watt, VAR coordinate pair, that, in combination with four other
watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_VAR_Pt3
- This tag is used as the VAR coordinate in the
third watt, VAR coordinate pair, that, in combination with four other watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_VAR_Pt4
- This tag is used as the VAR coordinate in the
fourth watt, VAR coordinate pair, that, in combination with four other
watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......