CGCM-DLR Unit Configuration
Chapter
4
Undervoltage
•
Setpoint - Establishes the undervoltage setpoint. This setpoint is stored in
tag
Undr_V_Setpt
in the configuration table and scaled in per cent rated
generator volts.
•
Delay - Establishes the time the generator voltage must be below the
undervoltage setpoint before the unit annunciates an undervoltage fault.
This setpoint is stored in tag
Undr_V_TimeDly
in the configuration table
and scaled in seconds.
Compensation Settings
•
Droop Percentage - Establishes the voltage droop level at rated load when
operating in Voltage Droop (reactive current compensation) mode. This
setting determines the change in voltage setpoint that is expressed in
percent of rated voltage. A setting of 5, for example, results in the voltage
setpoint changing by 5% of rated voltage for a change in kVAR equal to the
rated kVA. The tag
V_DroopSetpt
in the Configuration table stores this
parameter.
•
Line Drop Voltage Compensation - Establishes the output voltage increase
at rated current. Tag
LineDropComp
in the Configuration table stores
this parameter.
Related Parameters
•
GenRated_V
•
GenRated_I
•
GenRated_W
•
SoftStartTime
•
EngineIdle
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......