166
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 7
Troubleshooting
Voltage output is greater than
setpoint
AVR not selected / enabled
Check excitation AVR select
Correct Logix controller logic or I/O
as required
Wiring error
Check wiring for excitation current
output, VT inputs, fuses open,
grounding, and PMG/supply
Correct wiring as required
Gain mis-adjusted
Check gains that are entered into
CGCM-DLR unit configuration
Calculate / adjust as required
Excitation limiting active
Check UEL active input
Correct UEL configuration or change
operating point
Droop compensation is driving up
the voltage
Check Droop Enable
Adjust/disable droop compensation
Voltage is erratic or unstable
Gain mis-adjusted
Check gains that are entered into
CGCM-DLR unit configuration
Calculate / adjust as required
Wiring error
Check wiring for excitation current
output, VT inputs, fuses open,
grounding, and PMG/supply
Correct wiring as required
Prime mover is unstable
Check prime mover governor
operation
Correct as required
Excitation limiting active
Check UEL/OEL active input
Correct UEL/OEL configuration or
change operating point
Table 20 - Excitation Control - AVR
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......