Appendix E
Detailed CGCM-DLR Unit Tag Descriptions
•
DeadBusGenV_LoLim
- This tag configures the minimum voltage that
must be present on the generator to allow the breaker to close under a
Dead Bus condition.
•
DeadBusGenV_HiLim
- This tag configures the maximum voltage that
must be present on the generator to allow the breaker to close under a
Dead Bus condition.
•
DeadBusClosureEn
– Setting this tag to 1 lets the generator achieve
breaker closure with a dead bus.
•
BusA_PhOffset
- This tag configures a phase angle added to the measured
bus A phase angle. It is used to compensate for phase shift across sensing
transformers.
•
BusA_V_Scaler
- This tag configures a multiplier by which the measured
bus A voltage is multiplied. It is used to compensate for ratio error across
sensing transformers.
•
BusB_PhOffset
- This tag configures a phase angle added to the measured
bus B phase angle. It is used to compensate for phase shift across sensing
transformers.
•
BusB_V_Scaler
- This tag configures a multiplier by which the measured
bus B voltage is multiplied. It is used to compensate for ratio error across
sensing transformers.
•
BusA_B_Select
– This tag selects which reference bus the CGCM-DLR
unit attempts to synchronize to.
•
V_Match
Gain-This tag sets the Proportional Gain parameter for Voltage
Matching mode
Synchronizing Outputs from CGCM-DLR Unit
•
SyncDeadBus
- This tag indicates that all conditions have been to allow a
DeadBus synchronization
•
AutoSync
– This tag follows the AutoSyncEn tag setting in the Scheduled
Write tag.
•
CheckSync
- This tag follows the CheckSyncEn tag setting in the
Scheduled Write tag.
•
PermissiveSync
- This tag follows the PermissiveSyncEn tag setting in the
Scheduled Write tag.
•
SyncFailure
– This tag indicates that the synchronization attempt failed.
•
UndefinedSyncMode
– This tag indicates that a synchronization was
initiated when none of the synchronization modes were asserted.
•
SyncModeConflict
– This tag indicates that multiple Synchronization
modes were selected.
•
BusRot_ABC_ACB
– This tag reports the rotation sequence of the
reference bus in 3-phase metering. In single phase metering, these bits
reflect the configuration value.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......