116
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 4
CGCM-DLR Unit Configuration
•
Under-frequency Delay - Establishes the amount of time in seconds that
the frequency must be below the under-frequency setpoint before the unit
annunciates the fault. This parameter is stored in tag
UndrFreqTimeDly
in the configuration table.
Related Parameters
•
EngineIdle
•
SoftStartTime
Power Page
The Power page is used to configure parameters that are related to reverse power
and reverse reactive power protection. A higher setpoint value corresponds to
larger reverse power or VAR flow before a fault is declared.
•
Reverse kW setpoint - Establishes the generator reverse kW setpoint in
percent of rated VA. The tag
Rev_kW_Setpt
stores this value in the
configuration table.
•
Reverse kW Fault Delay - Establishes the amount of time in seconds that
the reverse kW must be above the reverse kW setpoint before the
CGCM-DLR annunciates the fault. This parameter is stored in tag
Rev_kW_TimeDly
in the configuration table.
•
Reverse kVAR setpoint - Establishes the generator reverse kVAR setpoint
in percent of rated VA. The tag
Rev_kVAR_Setpt
stores this value in the
configuration table.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......