ABB | SACE Tmax XT
Protections | 7 - Standard Protections
47 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
I Protection
I
I3
t
I
Function
If the current of one or more phases exceeds threshold I3, the protection trips and, after a non-programmable
fixed time, transmits the TRIP command.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 87)
• the graph with trip curve (page 96)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu.
ON
Threshold I3
Establishes the value that activates the protection.
The value is given as both absolute value (A) and relative value (In) and
can be set within the range: 1.5 In to 15 In, in 0.1 In steps
4 In
ZoneSelectivity
Activates/deactivates the function
NOTE
: if at least two of the selectivity S, S2, I, 2I and MCR are
enabled, the input and output are shared with the OR function;
it is sufficient that even a selectivity is activated to stimulate
inputs and outputs
OFF
StartUp enable
Activates/deactivates the function and availability of the associated
parameters on the display (page 77)
OFF
StartUp
Threshold
Protection threshold valid during Startup time, in the conditions in
which the function is activated (page 77)
The value is given as both absolute value (A) and relative value (In) and
can be set within the range: 1.5 In to 15 In, in 0.1 In steps
1,5 In
StartUp Time
This is the time for which the StartUp threshold remains activated and
is calculated from the moment the activation Threshold is exceeded
(page 77)
The value is given in seconds and can be set within the range: 0.1 s to
30 s, in 0.01 s steps
0.1 s
Ekip M Touch
With Ekip M Touch, I protection is inhibited for 100 ms if the currents detected by the Trip unit cross zero
when at least one is present (0.25 In fixed control threshold).
Limitations and additional functions
• threshold I3 must be higher than threshold I2 (if S and I protections are activated)
• I protection can be activated with MCR protection disabled
• the block functions can also be accessed by means of the service connector (via Ekip Connect) or
communication via system bus (page 78)
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...