ABB | SACE Tmax XT
External electronic accessories | 12 - Ekip Synchrocheck
177 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Continued from the previous page
Parameter
Description
Default
Secondary voltage
Secondary voltage of the transformer; the value is given as absolute value
(Volts) and can be set within the range: 100 V to 120 V in variable steps.
100 V
Concatenated Ref
Line-to-line voltage entering the module among the 3 installation voltages U12
Contact Type
Defines the rest status of the contact with synchronism not present
between: open (NO) and closed (NC)
NO
(1)
parameter not available with busbar active and Auto deadbar detect= Manual
(2)
with dead busbar and configuration: Reversed, the roles of the internal and external voltages are reversed
(3)
10% hysteresis is applied to the minimum voltage condition: once reached, the condition is lost if the
voltage drops below 90% of the set limit
(4)
parameter not available with dead busbar and Auto deadbar detect= Manual
NOTE:
all the thresholds have ±10% tolerance with the exception of:
• Voltage Delta; the tolerance is the higher value between: ±10% of the set threshold and 0.5%
Un (with Un > 220 V) or 1% Un (with Un
≤
220V)
• Frequency Delta; the tolerance is the higher value between ±10% of the set threshold and 0.02
Hz
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter
Description
Default
Frequency
check
Activates (ON) or deactivates (OFF) frequency control for synchronism
assessment
ON
Phase check
Activates (ON) or deactivates (OFF) phase control for synchronism assessment ON
Evaluate CB
status
Activates (YES) or deactivates (NO) circuit-breaker open status control for
synchronism assessment
NOTE
:
fourth synchronism condition with busbar active; second
synchronism condition with dead busbar
NO
Minimum
matching time
With active busbar, minimum time within which the
Delta Phase
condition must
be obtained
The value is given in seconds and can be set within the range: 100 ms to 3 s,
in 10 ms steps
NOTE
:
this is not a synchronism condition, but a parameter allowing a
discrimination to be made between correct and incorrect combinations of
the Delta Frequency and Delta Phase conditions. Owing to worst case
latencies, the time that effectively elapses before synchronism is
recognized may be longer than the set time (approx. 20 ms)
100 ms
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...