ABB | SACE Tmax XT
128 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Settings | 1 - Main settings
Configuration
The
Circuit breaker-Configuration
menu, allowing the presence of the
External neutral
sensor to be activated,
is available for the 3P CB (page 188).
Activation of the configuration with
External neutral
(3P + N) enables:
• histograms of phase Ne in the
Histograms
page
• neutral current measurements
• submenu for configuring the Neutral protection (
Neutral Protection
)
• neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Ground protection
In the earth
Circuit-breaker-Protections
menu of the LSIG version of Ekip Touch you can:
• activate/deactivate the presence of external toroid S.G.R and relative Gext protection (page 187, 79).
• activate the presence of Rc Toroid and relative protection (page 187, 82).
• activate/deactivate the MDGF transformer presence and relative MDGF protection.
NOTE:
Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; Toroid presence in the menu can only be deactivated afterwards
by replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
Line frequency
Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and 60 Hz.
NOTE:
the measurements are taken on the basis of the set grid frequency: incorrect configuration
of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.
Modules
The
Modules
menu provides various options:
Parameter
Description
Default
Local/Remote
The parameter defines the mode in which the parameters are written
in the unit:
•
Local
: parameter editing only via the display or service connector
•
Remote
: parameter editing only remotely (Ekip Com modules)
NOTES
:
•
the Remote mode requires the presence of auxiliary
power supply and Ekip Com modules, otherwise it disables
automatically
•
However, the Local/Remote parameter can still be edited in
the Remote mode
Local
Local bus
The parameter enables communication between the Trip unit and
modules installed via terminal box or outside the unit to be activated.
Correct communication between unit and modules is confirmed by:
• population of the
Modules
menu with all the modules connected
• Power Leds of the modules on and synchronized like the power led
of Ekip Touch
• absence of Local Bus alarm in the diagnosis bar
Off
Ekip Measuring
Menu with the parameters of the module Measurement (page 137)
-
Menu of every module connected and detected (from page 141)
Functions
Access to the
LOCAL Switch On
and
RESET signaling
functions (from
page 84)
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...