S Protection
S
I2
t
t2
I
Function
If the current of one or more phases exceeds threshold I2, the protection trips and, after a time established
by the value read and by the parameter settings, transmits the TRIP command.
To check and simulate the trip times in relation to all the parameters, please consult:
• the summary table of the protections with the calculation formulas (page 87)
• the graph with trip curve (page 94)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu.
OFF
Trip Enable
Activates/deactivates transmission of the open command. if disabled,
the alarm and exceedance of protection time are only managed as
information.
ON
Curve
Establishes curve dynamics and the threshold or trip time calculation:
• t = k: fixed time trip
• t = k/I
2
: inverse time-delay dynamic trip
t = k
Threshold I2
Establishes the value that activates the protection and contributes
towards calculating the trip time.
The value is given as both absolute value (A) and relative value (In) and
can be set within the range: 0.6 In to 10 In, in 0.1 In steps
4 In
Time t2
It is the trip time or contributes towards timing calculation, depending
on the type of curve selected.
The value is given in seconds and can be set within the range: 0.05 s
to 0.8 s, in 0.01 s steps
0,05 s
Thermal
memory
Activates/deactivates the thermal memory function (page 75)
NOTE
:the function is only available with curve t=k/I
2
OFF
ZoneSelectivity
Activates/deactivates the function and selectivity time availability on
the display (page 75)
NOTE
:the function is only available with curve t=k
OFF
Selectivity time
This is the trip time of the protection with the zone selectivity function
activated and selectivity input not present (page 75)
The value is given in seconds and can be set within the range: 0.04 s
to 0.2 s, in 0.01 s steps
0,04 s
StartUp enable
Activates/deactivates the function and availability of the associated
parameters on the display (page 78)
OFF
StartUp
Threshold
Protection threshold valid during Startup time, in the conditions in
which the function is activated (page 78)
The value is given as both absolute value (A) and relative value (In) and
can be set within the range: 0.6 In to 10 In, in 0.1 In steps
0,6 In
StartUp Time
This is the time for which the StartUp threshold remains activated and
is calculated from the moment the activation Threshold is exceeded
(page 78)
The value is given in seconds and can be set within the range: 0.1 s to
30 s, in 0.01 s steps
0.1 s
Limitations and additional functions
• threshold I2 must be higher than threshold I1 (if S protection is activated)
• in the presence of curve t= k/I
2
, the protection trip time is forced to t2 if the calculation results give a
theoretical value lower than t2 itself
• the block functions and type of selectivity can also be accessed by means of the service connector (via
Ekip Connect) or communication via system bus (page 75)
• with CB in UL standard configuration, the maximum value of t2 is 400 ms
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...