58 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Protections | 9 - Voltage Advanced protections
Continued from the previous page
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Curve
Allows the operating mode, Step or Lin, to be selected
Scal
Threshold I21
Establishes the value that activates the protection and contributes
towards calculating the trip time.
The value is given as both absolute value (Amperes) and relative value
(In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
1 In
Threshold Ul2
It is the voltage that determines the change in trip threshold I21; the
behavior differs, depending on the mode selected
(1)
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.2 Un to 1 Un in 0.01 Un steps
1 Un
Threshold Uh2
The parameter is shown by the Lin curve and contributes towards I21
trip threshold calculation:
• with voltage reading < Uh2 (and
≥
Ul2), the threshold changes
gradually
(1)
• with voltage reading
≥
Uh2, the threshold is I21
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.2 Un to 1 Un in 0.01 Un steps
1 Un
Threshold Ks2
I21 threshold calculation constant.
The value is given as percentage of threshold I21 and can be set
within the range: 0.1 I21 to 1 I21, in 0.01 steps
0,6 I21
Time t20
This is the trip time of the protection.
The value is given in seconds and can be set within the range: 0.05 s
to 30 s, in 0.01 s steps
0.1 s
(1)
Trip threshold (depending on the operating curve)
Mode
Voltage reading
Trip threshold
Scal
< UI2
Ks2 x I21
≥
UI2
I21
Lin
< UIs
Ks2 x I21
≥
Ul2 (e < Uh2)
((I21 x ( 1 - Ks2 ) x ( U
mis
- Uh2 ) ) / (Uh2 - Ul2) ) + I21
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 78).
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...