ABB | SACE Tmax XT
38 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Interface and menus | 4 - Menu
Installation menu
If Ekip Touch detects that
Rating Plug
or
Ekip Measuring
have not been installed properly, it signals an alarm
(page 19) and completes
Settings
menu with the specific installation section:
Menu
Submenus 1
Submenus 2
Commands
Circuit Breaker
Installation
Rating Plug
Install
Ekip Measuring
Install
Correct installation is confirmed by a message on the display and disappearance of the alarm signal and
installation menu.
NOTE:
availability of submenus depends on the module, which appears to have not been
installed
Test Menu
Menu
Submenus
Description, parameters and Comman-
ds
Page
Autotest
-
Autotest command
Trip Test
-
TRIP command
Test CB
-
Close CB
,
Open CB
Ekip CI
-
Autotest command
Ekip Signalling 2K
(1)
Ekip Signalling 2K-1
(1)
Module autotest command
Ekip Signalling 2K-2
(1)
Ekip Signalling 2K-3
(1)
ZoneSelectivity
(2)
S Protection
(3)
Input
,
Force Output
,
Release Output
G Protection
(4)
Rc Test
(5)
-
Test instructions
(1)
available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
(2)
available if Ekip Touch is on with auxiliary supply
(3)
available with S and/or S2 and/or D protection enabled, for S protection the set curve must be t=k
(4)
available with G and/or Gext and/or MDGF and/or D protection enabled and curve t=k
(5)
available with Rating Plug and Rc toroid present
(6)
available if the Ekip CI module is connected and detected by Ekip Touch
About Menu
Menu
Submenus
Information provided
Protection Unit
-
Information about Ekip Touch: Mainboard serial
number, Trip unit serial number, type, version,
standard, SW version, date and time, language
Circuit Breaker
-
CB information: TAG name, CB name, rated current,
number of poles, CB status and position, total
operations, CB serial number
IEC61557-12
(1)
-
Status of 1% measurements (from
Class 1 Power
& Energy Metering
package), serial number of
assembly and current sensors connected
Feature Collection
-
List of tripped protections in Trip unit
Modules
Modul x
(2)
Module information: serial number, SW version,
status of inputs/outputs/contacts (if present)
(1)
available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it has been
previously activated
(2)
available if one or more modules are connected and detected by unit
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...