Management operations | 2 - Maintenance and troubleshooting
21 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Continued from the previous page
Protections
In the event of protection or measurement alarms, the associated signals are reported:
Signal
Type of alarm
Trip Test
Trip test performed signal. Press
iTEST
to reset the message
Protection timing (for example: L
timing)
Specific protection in time delay mode
Protection prealarm (for example:
Prealarm G)
Specific protection in prealarm
Protection (Trip off) [for example: S
(Trip off) ]
Specific protection, configured with trip disabled, in alarm state
2I Protection Active
2I Protection active
Load LC1 / Load LC2
Current threshold 1 I1 / 2 I1 exceeded and in alarm state
Iw1 Warning / Iw2 Warning
Current threshold Iw1 / Iw2 exceeded and in alarm state
Harmonic dist.
Harmonic Distortion protection in alarm state
Power factor
Power factor measurement (cos
φ
) less than set threshold
Phase cycle
Phase sequence protection in alarm state
Frequency
Frequency measured off range (<30 Hz or >80 Hz)
5th harmonic above Th / I sopra Th
/ THD I above Th / THD V above Th
Single or total harmonic measurement above threshold
Faults, causes and remedies
A list of possible faulty situations for Ekip Touch, their possible causes and suggestions about how to resolve
them are given below.
NOTE:
check error messages on display before consulting the table; if the suggestions given
fail to resolve the problem, call the ABB assistance service and provide the report
produced by the Ekip Connect software if possible
Faults
Possible causes
Suggestions
The circuit-breaker doesn't close
when the closing pushbutton is
pressed
The trip signal of the protection
trip unit has not been reset
Press the TU mechanical reset
pushbutton or operate the
electrical reset remotely.
The open-position key lock or
padlock is activated
Unlock the lock in open position
using the relevant key
The circuit-breaker is in an
intermediate position between
connected and isolated for test
or between isolated for test and
disconnected
Complete the rack-in operation
The undervoltage coil is not
energized
Check the power supply circuit
and the power supply voltage
The opening coil is permanently
energized
Correct operating condition.
The trip unit pushbutton is
pressed (withdrawable version)
Rotate the crank to complete
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...