ABB | SACE Tmax XT
Protections | 8 - Voltage protections
55 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
OV2 Protection
U16
t
t16
V
OV2
Function
OV2 protection functions in the same way as OV protection: the protection sends a TRIP command if one or
more line-to-line voltages detected by the unit exceed threshold U16 for longer than t16.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 100)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Threshold
U16
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un) and
can be set within the range: 1 Un to 1.5 Un in 0.001 Un steps
1,05 Un
Time t16
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 78).
Phase sequence protection
The
Phase Sequence
protection enables an alarm to be activated when the sequence of line-to-line voltages
is not aligned with the sequence set by the user.
The required sequence can be set in the
Settings
menu and the protection activated in the
Advanced
menu
(page 37 and page 35).
VU Protection
U14
t
t14
V
VU
Function
The protection trips if the line-to-line voltages read by the unit are unbalanced; the protection sends a TRIP
command if the detected unbalance exceeds threshold U14 for longer than t14.
The protection excludes itself if the maximum value of the line-to-line voltage is less than 0.3 Un
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 100)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Threshold
U14
Establishes the unbalance value that trips the protection.
Unbalance is expressed in percentage value and is calculated in the
following way: % Unba = 100 x (Δmax U
mi
) / U
mi
in range: 2% to 90% in 1%
steps.
NOTE
: Δmax U
mi
: maximum deviation among the three voltages
calculated by comparing each line-to-line voltage with the mean value;
U
mi
: mean value of the line-to-line voltages
50 %
Time t14
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 0.5 s to 60 s, in 0.5 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 78).
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...