ABB | SACE Tmax XT
Ekip Touch - Measurements | 5 - Network Analyzer
123 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Spikes
The
Spikes
counter should be understood as increase of the RMS value of the line-to-line voltage above the
set
V Spike Threshold
threshold for less than 40 ms (short time voltage spike).
The counter is available in the two submenus
Counters
-
Day
-
1 and Counters
-
Cumulative
(previous day or
cumulative)
NOTE:
Since the counter is based on the RMS value calculation, two rapid voltage spikes of
equal duration may be evaluated differently, depending on their amplitude:
t
t
Increase detected
Increase not detected
Additional List
Counters
(Interruptions)
Description
Last time stamp
Date and time of last recording of the
Spikes
counter
Last value
Value of last swell above
Spikes
[V] threshold
Last duration
Duration of last swell above
Spikes
[ms] threshold
Actual number of S.
Spikes
count for the current day
Actual [day -2 ... day -7]
number of S.
Spikes
count of the last seven days of activity, calculated using the internal
clock of the unit
Sags
Certain counters relating to sags are available in the
Counters
-
Day
-
1 and Counters
-
Cumulative
submenus:
Counters
(Interruptions)
Description
Sags Short
Counts the number of times that any line-to-line voltage falls below the
V sag
Th Short
threshold for longer than
V sag dur Short
Sags Middle
Counts the number of times that any line-to-line voltage falls below the
V sag
Th Middle
threshold for longer than
V sag dur Middle
Sags Long
Counts the number of times that any line-to-line voltage falls below the
V sag
Th Long
threshold for longer than
V sag dur Long
The count refers to the reference menu interval (previous day or cumulative)
NOTE:
since an event may fall under more than one category, only the counter of the main
type (Long > Middle > Short) is increased
Additional List
Counters
(Interruptions)
Description
Last time stamp
Date and time of last recording of the
Sags Short
counter
Sags Middle
Value of last sag below the
Sags Short
[V] threshold
Sags Long
Duration of last sag below the
Sags Short
[ms] threshold
Actual number of S.
Sags Short
count for the current day
Actual [day -2 ... day -7]
number of S.
Sags Short
count of the last seven days of activity, calculated using the internal
clock of the unit
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...