Synchrocheck
With regard to closing the interconnection switch, the
Ekip Synchrocheck
module recognizes and reports
whether there are synchronism conditions between two independent voltage sources (example: generator
+ grid).
A description of the module, the protection function and performance is given in the chapter dedicated to
the modules (page 174).
Programmable Functions and
Commands
Eight commands are available, with activation that can be programmed on the basis of signals or events.
Distributed among different Ekip Touch menus, the commands are:
Name
Description
Path (page)
External Trip
Sends a TRIP command
Advanced
-
Functions
(35)
Trip RESET
Reset of the trip signal
Turn on SET B
Changes the protections set, from Set A to Set B
2I Mode
It activates 2I protection, if configured for this
function
Advanced
-
Functions
-
2I
Menu
(50)
RESET Energy
Resets the energy meters
Measurements
-
Energy
YO Command
Sends an open command to YO
Settings
-
Functions
(37)
YC Command
Sends a close command to YC
(1)
LOCAL Switch On
Changes the configuration, from Remote to Local
Settings
-
Modules
-
Functions
(37)
Signaling RESET
Reset the contacts of the signalling modules
(1)
the MOE-E storage command must be present
Parameters
Each command provides two programming parameters:
Parameter
Description
Default
Function
Event or several command activation events (up to eight, in AND
or OR logic configuration). The Custom configuration can be
programmed via Ekip Connect.
Deactivated
Delay
This is the minimum time the expected event must be present in order
to activate the command; the value is given in seconds and can be set
within a range: 0 s to 100 s, in 0.1 s steps
0 s
IMPORTANT: the commands are sent if all the operating conditions expected by the
unit are present (connections, power supplies, alarms, etc.)
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...