Ekip Touch - Measurements | 4 - Datalogger
Parameters 2
The
Datalogger 1
and
Datalogger 2
submenus (available if the number of dataloggers selected is: 2) contain
the following options:
Parameter
Description
Default
Stop Event
Trigger event at which the recording is to be interrupted; the main
protection options (trips, timings, alarms) and the actuator status (open/
closed) are displayed.
The Custom option can be configured via Ekip Connect
None
Stop delay
Recording interruption delay, calculated from the trigger; the value is given
in seconds and can be set within a range: 0 s to 10 s, in 0.01 s steps
0.01 s
Restart
Recording start command
Stop
Manual recording stop command
Memory Type
Ekip Connect enables the
Memory Type
(Non volatile/Volatile) to be selected:
•
Non volatile
: Ekip Touch maintains the registration even when off; the life of the internal battery of the unit
can be sensibly less than the declared value in the absence of auxiliary power supply.
•
Volatile
: Ekip Touch loses the recording if it is switched off; when the unit is switched on again, the datalogger
automatically restarts, losing the previously stored data.
The parameter is configured by default as Non volatile.
Signallings
If there is a recording present, Ekip Touch provides the information on the diagnosis bar (DataLog available).
NOTE:
Ekip Touch provides a general indication of recording availability in the configuration
with 2 dataloggers: use Ekip Connect to identify which of the 2 recordings (or both) is
available
Ekip Connect
Ekip Connect 3 has two specific areas for the Datalogger function:
•
Datalogger
for configuring the recording parameters with a user-friendly interface, and for downloading
the recordings
•
Data Viewer
for opening and consulting the recordings
Both areas are available in the Tools menu of Ekip Connect.
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...