ABB | SACE Tmax XT
160 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
External electronic accessories | 8 - Ekip Com IEC 61850
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the
Settings
menu (page 37).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter
Description
Default
Static IP address ON
Defines whether the module has the dynamic (
Off
) or static
(
On
) IP address.
Se = On all the associated parameters are enabled
OFF
Static address IP address
Enables the static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address of the
node to which the module is connected to be selected
0.0.0.0
Enable SNTP client
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled.
OFF
SNTP Server Addr.
Allows the network server that supplies the SNTP to be set.
0.0.0.0
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the module
correctly:
Information
Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
can be set via the menu in the event of a static IP.
NOTE
:
without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the
modules belong and enables modules to be searched for within a defined set
of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence of
several subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Cfg file
Name of the configuration file uploaded to the modules
Cfg file error
Code of the error concerning the configuration file (0 = no error)
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...