ABB | SACE Tmax XT
176 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
External electronic accessories | 12 - Ekip Synchrocheck
Continued from the previous page
LEDs
Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present, flashing not synchronized with the Power
led of Ekip Touch (two fast flashes per second): module on and communication with
Trip unit absent
O SC
Indicate the status of the contacts of each output:
• off: contact open
• on: contact closed
NOTE
:
The LED shows the output status: it indicates synchronization OK or
KO, depending on the contact rest configuration (normally open or closed)
Configurations via menu
The specific configuration area will activate in the
Advanced
-
Synchrocheck
menu if the
Ekip Synchrocheck
module is detected correctly by Ekip Touch.
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
Off
Dead bar option
On = busbar activated; Off = dead busbar present
Off
Udead
Threshold
(1)(2)
Maximum external voltage (with dead busbar and configuration:
Normal
(2)
is the first synchronism condition)
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.02 Un to 2 Un, in 0.001 Un steps
0.2 Un
Ulive
Threshold
(2)(3)
Minimum voltage for starting monitoring of external voltage (with busbar
activated) or internal voltage (with dead busbar and
Normal
configuration)
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.5 Un to 1.1 Un, in 0.001 Un steps
0.5 Un
Stability Time
Minimum time within which the
Ulive Threshold
condition must be
obtained in order to activate voltage monitoring
The value is given in seconds and can be set within the range: 100 ms to
30 s, in 1 ms steps
1 s
Delta Voltage
Maximum difference between internal and external voltage (first
synchronism condition)
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.02 Un to 0.12 Un, in 0.001 Un steps
0.12 Un
Delta frequency
(4)
Maximum difference between internal and external frequency (second
synchronism condition)
The value is given in Hertz and can be set within the range: 0.1 Hz to 1
Hz in 0.1 Hz steps
0.1 Hz
Delta phase
(4)
Maximum difference between internal and external phase (third
synchronism condition)
The value is given in degrees and can be set within the range: 5° to 50° in
5° steps
50 °
Dead bar
configuration
With dead busbar and generator:
• Reversed =
Ekip Synchrocheck
/external contacts connected to the
generator
• Normal =
Ekip Synchrocheck
/external contacts connected to the grid
Standard
Auto Live-dead
detect
Enables automatic synchronism control to be activated:
• Manual = Ekip Touch considers the
Dead bar option
parameter
• Automatic = Ekip Touch automatically assesses the configuration to be
actuated between the dead busbar and active busbar
Manual
Auto Deadbar
detect
Configuration for detecting dead busbar:
•
Manual
= Ekip Touch considers the
Dead bar configuration
parameter
•
Automatic
= Ekip Touch automatically assesses the configuration to be
actuated between:
Reversed
and
Normal
Manual
Primary voltage
Rated voltage Un of installation; the value is given as absolute value
(Volts) and can be set within the range: 100 V to 1150 V in variable steps.
100 V
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...