ABB | SACE Tmax XT
External electronic accessories | 9 - Ekip Link
165 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Continued from the previous page
Parameter
Description
Default
Disable Gratuitous ARP
Permits (Enabled ARP) the periodic generation of a Gratuituos
ARP message, used by Ekip Connect to rapidly find the
modules via Ethernet scan without knowing the IP address
beforehand
ARP Enabled
Password protected
access
Enables the writing operations performed via the network to be
protected by a password (Request password)
Standard
mode
Password Modbus TCP
With access protected by enabled password, this is the
password to use before each writing session
(2)
.
Local access
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration
Remote Link configurations
Regarding the Link functions, the following further parameters are available:
Parameter
Description
Default
Link Actor (1÷15)
IP address of each actor (from 1 to 15)
0.0.0.0
Remote Programmable
Status (A÷D)
Configuration parameters of the configurable states:
• selection of actor (actor from 1 to 15) which activates the
programmable status
• event of the actor that determines change of programmable
status
Actor 1
None
Remote Status word
(A÷D)
Configuration parameters of the words:
• selection of actor (actor from 1 to 15) from which the word
status is taken
• selection of the taken word
None
1 global
Diagnostic
Active (Passive diagnosis) or deactivated (No diagnosis) cabled
selectivity diagnosis
No Diagnostic
Diagnostic check timeout
30 s, 1 min, 10 min, 60 min diagnosis frequency intervals
available, if activated
30 seconds
Zone Selectivity Type
Configuration of hardware selectivity (Only HW) or hardware
and logic (Mixed)
HW only
Repeat Configuration
mask
Interactive mask for selecting selectivity to be sent also to the
upper levels (even if not active in the programmed device)
0x0000
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information
Description
HW and Boot version
General module information
Flash CRC status and
result
Information about the correctness of the SW in the module
Ekip Link status
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server
Synchronization
State of synchronism with SNTP server
IEEE 1558 status
Valid with Master IEEE 1588=
ON
, notifies the presence (Slave or PTP Master
Active) or absence (PTP Master but Passive) of a higher level master
Remote Link information
Regarding the Link functions, the following further parameters are available:
Information
Description
Line Congruency detection
Information about the state and inconsistency of HW and logic
selectivity (state and type of selectivity inconsistent)
Remote Programmable Status
Status (true/false) of remote programmable statuses A, B, C and D
Remote Status Word
Value of remote programmable Words A, B, C, D
Logic Zone Selectivity
Logic selectivity states (inputs and outputs)
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...