ABB | SACE Tmax XT
76 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Protections | 15 - Additional protections and functions
Continued from the previous page
Configuration
To correctly configure the selectivity network of one or more protections:
1. Connect zone selectivity outputs of the same type (example: Szo) of devices belonging to the same zone,
to the zone selectivity input of the device immediately upstream (example: Szi).
2. Connect all the Szc of devices in the same network together.
3. Time t2 must be configured at t2 sel + 50 ms or more, with the exclusion of the device further along its
network.
Logic table
The table includes all cases in which, with zone selectivity enabled in the device, an alarm condition occurs
or a zone selectivity signal is received from another device.
NOTES:
• the table gives the S protection cases, but is also valid for the other protections: G, S2, I, 2I,
MCR, Gext and MDGF, each with its respective connections
• if the selectivities of protections that share the same connections are active at the same time
(example: S, S2, I, 2I and MCR), the inputs/outputs are managed with OR logic
Condition
Szi
Szo
Tripping time Remarks
If < I2
0
0
No TRIP
TRIP Il device not in alarm status
If < I2
1
1
No TRIP
The device is not in the alarm status, but sends the
selecitivity signal received from the device upstream
If > I2
0
1
t2 sel
(1)
The device is in the alarm status and is the first to detect
the fault: trips within time t2 sel
(1)
If > I2
1
1
t2
(2)
The device is in the alarm status but is not the first to
detect the fault: trips within time t2
(2)
D zone selectivity Protection
Foreword
This function, which can be activated for D protection (if available and enabled), enables devices belonging
to the same installation (including Ekip Touch) to be connected together so as to handle the trip commands
in a better way in the case of D protection.
It is especially useful in ring and grid type systems where, besides the zone, it is essential to also define the
direction of the power flow that supplies the fault.
The function allows the devices to be coordinated so that, if a fault occurs:
• The device nearest to the fault trips
• The other devices are blocked for a programmable time
NOTES:
• connection can be made between ABB devices that have the zone selectivity function
• disable the zone selectivities of protections S, S2, I, 2I, MCR, G, Gext and MDGF to correctly
use the selectivity D function
Characteristics
Ekip Touch has five selectivity connections, located on the upper terminal box of the CB:
Name
Type
Description
Denomintion for D
Szi
Input
Forward direction selectivity input
DFin
Szo
Output
Forward direction selectivity output
DFout
Gzi
Input
Backward direction selectivity input
Dbin
Gzo
Output
Backward direction selectivity output
Dbout
Szc
Common
Common connection of selectivity network
SZc
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...