ABB | SACE Tmax XT
22 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Management operations | 2 - Maintenance and troubleshooting
Continued from the previous page
Faults
Possible causes
Suggestions
The circuit-breaker doesn't close
when the closing coil is powered
The trip signal of the protection
trip unit has not been reset
Press the TU Reset button
The power supply voltage of the
auxiliary circuits is too low
Measure the voltage: it should not
be lower than 70% of the rated
voltage of the coil
The power supply voltage is
different from that indicated on the
rating plate
Check the voltage on the rating
plate
The cables of the coil are not
inserted correctly in the terminals
Make sure there is continuity
between cable and terminal and if
necessary reconnect the cables of
the coil to the terminals
The connections in the power
supply circuit are wrong
Check the connections using the
relevant wiring diagram
The closing coil is damaged
Replace the coil
The operating mechanism is
blocked
Perform the closing operation
manually; if the fault persists
contact ABB
The open position key lock is
activated
Unlock the lock in open position
using the relevant key
The circuit-breaker is in an
intermediate position between
connected and test or the trip
unit pushbutton is pressed
(withdrawable version)
Complete the rack-in operation
The undervoltage coil is not
energized
Make sure that undervoltage coil
is energized properly
The opening coil is permanently
energized
Correct operating condition. If
necessary, disconnect the power
from the opening coil
The racking out crank handle is
inserted (withdrawable version)
Remove the crank
The circuit-breaker doesn't open
when the opening pushbutton is
pressed
The operating mechanism is
blocked
Contact ABB
The circuit-breaker doesn't open
when the opening coil is powered
The operating mechanism is
blocked
Contact ABB
The power supply voltage of the
auxiliary circuits is too low
Measure the voltage: it should not
be lower than 85 % of the rated
voltage of the coil
The power supply voltage is
different from that indicated on the
rating plate
Use the correct voltage
The cables of the coil are not
inserted correctly in the terminals
Make sure there is continuity
between cable and terminal and if
necessary reconnect the cables of
the coil to the terminals
The connections of the power
supply circuit are wrong
Check the connections using the
relevant wiring diagram
The opening coil is damaged
Replace the coil
The circuit-breaker doesn't open
despite the command of the
undervoltage coil
The operating mechanism is
blocked
Perform the opening operation
manually; if the fault persists
contact ABB
It is not possible to charge the
closing springs by means of the
manual charging lever
The operating mechanism is
blocked
Contact ABB
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...