Protections | 15 - Additional protections and functions
83 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Current thresholds
Function
The Current thresholds allow checks to be set along the current lines, to be associated with the programmable
contacts of the
Ekip Signalling
modules (in all versions).
Two pairs of programmable contacts are available:
• Threshold 1 I1 and Threshold 2 I1, with control relating to I1
• Threshold Iw1 and Threshold Iw2, with control relating to In
The thresholds can be enabled and set in the Advanced - Signaling menu (page 35).
IMPORTANT:
• the current thresholds do not handle the trip, just the signal
• the function is activated if the trip unit is powered by auxiliary voltage
Parameters
Threshold
Available parameters
Default
Threshold 1 I1
Enable
: Activates the protection and availability of the threshold in the
menu
OFF
Threshold
: The value is given in percentage of threshold I1 and can be
set within the range: 50% I1 to 100% I1, in 1% steps.
50 % I1
Threshold 2 I1
Enable
: Activates the protection and availability of the threshold in the
menu
OFF
Threshold
: The value is given in percentage of threshold I1 and can be
set within the range: 50% I1 to 100% I1, in 1% steps.
75 % I1
Threshold Iw1
Enable
: Activates the protection and availability of the threshold in the
menu
OFF
Direction
: allows the user to choose whether to have the signal when
the current is higher (
Up
) or lower (
Down
) than the threshold.
Down
Threshold
: The value is given as both absolute value (Amperes) and
relative value (In) and can be set within the range: 0.1 In to 10 In, in
0.01 In steps
3 In
Threshold Iw2
Enable
: Activates the protection and availability of the threshold in the
menu
OFF
Direction
: allows the user to choose whether to have the signal when
the current is higher (
Up
) or lower (
Down
) than the threshold.
Up
Threshold
: The value is given as both absolute value (Amperes) and
relative value (In) and can be set within the range: 0.1 In to 10 In, in
0.01 In steps
3 In
Figure 33
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...