ABB | SACE Tmax XT
Ekip Touch - Measurements | 1 - Standard Measurements
109 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Measurements
1 - Standard Measurements
List
The Standard measurements are:
Parameter
Description
Page
Instantaneous currents
Phase current and earth fault measurements in real time
Events
List of events, status changes, alarms, recorded by the Trip unit
Trip
List of current protection trips (TRIP)
Min-Max measurements
History of minimum and maximum currents, recorded at a settable
interval
Maintenance
CB status: contact wear and last maintenance
Operation counters
Number of mechanical and electrical operations
Instantaneous currents
The instantaneous currents, available in the
Measurements
pages, are real time measurements of the phase
and earth fault currents expressed in root mean square value; the monitor time and performance depend on
the rated current defined by the
Rating plug
(In):
Measurement
Monitor time
(min-max)
Normal operating
range
Accuracy of
value read
(1)
Phase currents
(4)
0,004 ÷ 64 In
0,2 ÷ 1,2 In
1%
(3)
Internal earth fault current
(2)
0,08 ÷ 64 In
0,2 ÷ 1,2 In
2 %
(3)
External earth fault current
(2) (5)
0,08 ÷ 4 In
0,2 ÷ 1,2 In
2 %
Residual current
(2) (5)
2 ÷ 32 A
5 %
(1)
the accuracies refer to normal operating ranges, as established by IEC 61557-12
(2)
available with LSIG versions
(3)
accuracies based on Ekip Touch and Ekip Touch Measuring without Class 1 Power & Energy Metering
package; if the Class 1 Power & Energy Metering package is present and for all other trip unit models, check
the indicated performance values from page 116
(4)
the higher phase currents are also available in the Histograms, Measuring instruments and Measurement
summary pages
(5)
available by activating the presence of toroid S.G.R or Rc
Special representations
Type of measurement
Measurement <
min value
Measurement <
max value
“_ _ _” displayed:
(not available) due to
Internal earth fault and
phase currents
. . . .
> [64 In]
Sensors disconnected
External earth fault
current
. . . .
> [4 In toroid]
Toroid not activated and/
or disconnected
Residual current
. . . .
> 32 A
Toroid not activated and/
or disconnected
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...