ABB | SACE Tmax XT
174 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
External electronic accessories | 12 - Ekip Synchrocheck
12 - Ekip Synchrocheck
Ekip Synchrocheck
is an accessory module that is used to control closing of an actuator when synchronism
conditions, programmable by the user, exist.
To actuate synchronism:
•
Ekip Synchrocheck
and the internal sockets measure, respectively, the voltage on the external contacts
(external voltage) and on the internal contacts (internal voltage) of the actuator
•
Ekip Synchrocheck
manages a closing contact
NOTES:
•
the actuator is described as a circuit-breaker in the following description and in the menus
•
with a generator and the actuator being configured: Normally, the external voltage is that of the
grid and the internal voltage is that of the generator
IMPORTANT: only one Ekip Synchrocheck can be installed on each CB
Mode
The module operates in two modes, configurable by the user (manual-mode configuration) or managed
automatically by the unit (automatic-mode configuration).
Conditions
Description
Busbar active
Operation with external voltage other than zero:
• synchronism search starts if the external voltage is (0.5 Un by default) or more, for
at least (1 s by default)
• synchronism is considered to have been reached if the differences between RMS
values and frequencies and the voltage phases are (0.12 Un, 0.1 Hz, and 50° by
default) or less
Dead busbar and
configuration:
Normal
Operation with one of the voltages nil:
• synchronism search starts if the internal voltage is (0.5 Un by default) or more, for
at least (1 s by default)
• synchronism is considered to have been reached if the external voltage is (0.2 Un
by default) or less, for at least (1 s by default)
NOTE:
with dead busbar and configuration: Reversed, the roles of the internal and external
voltages are reversed
Synchronism signal:
• is activated and maintained, after synchronism has been reached, for at least 0.2 s
• is deactivated when synchronism ends or the circuit-breaker is opened (with condition:
Evaluate CB status
= enabled) or communication with Ekip Touch is interrupted
Additional functions
Certain options can be remotely configured in the synchronism conditions described above:
• the open circuit-breaker condition can be added (disabled by default)
• removal of the frequency and phase controls can be disabled
IMPORTANT: to be able to disable the frequency and phase controls, first make sure
that the required frequency and phase correspondence between external and
internal contacts already exists
Connections
The module must be assembled in the first vacant slot of the terminal box after
Ekip Supply
, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document
; use AWG 22-16 cables with 1.4 mm maximum outer diameter for the external cabling.
To connect the module to Ekip Touch, please consult document
.
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...