ABB | SACE Tmax XT
Ekip Touch - Test | 1 - Test
133 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Test
1 - Test
Presentation
The test area can be accessed on the display; the commands available in this area allow certain functions of
the Trip unit to be checked; details of all the commands available in the Test menu are given below (page 38).
Ekip T&P with Ekip Connect has a
Test Protections
section where the presence of current or voltage alarm
signals can be simulated and times and trips can be checked.
Autotest
The Autotest command starts an automatic sequence of the display and leds so as to enable their operation
to be checked.
The sequence comprises the following test phases:
1. Screen with message “www.abb.com”.
2. Darkening of the display.
3. Color sequence with red, green, blue bands, with gradual increase of backlighting
4. Lighting up, for one second, of the Warning and Alarm leds.
NOTE:
auxiliary power supply must be present in order to check the gradual increase of
backlighting
Trip Test
Selection of the
Trip test
command accesses the dedicated page where the operator is asked to press the
iTEST
key to confirm the test operation.
An open command is transmitted to the Trip coil of the CB when the key is released.
IMPORTANT:
•
the open command is sent with the circuit-breaker closed and in the absence of current
•
following a command, the user is responsible for checking the effective change in
status of the actuator and the information displayed: make sure that there are no
alarms on the diagnosis bar before performing the test
NOTE: to reset the TRIP signal, go back to the HOME page and press the iTEST
key
or transmit a TRIP RESET command (via Ekip Connect or remotely)
Test CB
Selection of the
Test CB
command accesses a submenu with the
Open CB
and
Close CB
commands.
The commands allow opening coil YO and closing coil YC to be activated, respectively: a window with the
message "Test Executed" confirms that the command has been transmitted correctly.
Correct operation of the entire command system (Trip unit, Ekip Com Actuator and opening and closing coils)
is checked by opening and closing the circuit-breaker.
IMPORTANT:
•
the open and close commands of the coils only function when the Trip unit is on and
powered by an auxiliary supply
•
make sure that the coils are connected to the supply source
•
release operation is checked by the commands:
faults in Ekip Com Actuator or the
coils are not detected by the test
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...