background image

 

 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

Introduction 

Command Closing Coil: 

 

Command  Close  coil  is  used  to  switch  ON  the 
Power 

Circuit 

Breaker 

remotely. 

When 

commanded  it  releases  the  spring  charged 
mechanism  thus  ensuring  a  rapid  connection  of 
the  main  contacts.  The  Command  Close  coil 
offers an extended functionality in addition to all 
the  features  of  the  standard  closing  coil. 
Additional  connections  allow  it  to  be  wired  out 
through  the  trip  unit  to  be  commanded  through 
the  communications  bus.  An  optional  electrical 
close pushbutton that fits onto the breaker front 
fascia  is  available  to  command  the  accessory 
from the breaker directly. 
 

 

 

 

Table 1. 

 

Catalog No 

DC Voltage 

AC Voltage 

GCCC024DR 

24V 

  

GCCC030DR 

30V 

  

GCCC048R 

48V 

48V 

GCCC060DR 

60-72V 

  

GCCC120R 

110-130V  110-130V 

GCCC208AR 

  

208V 

GCCC240R 

220-240V  220-240V 

GCCC277R 

250V 

250-277V 

 

                       

   

 

 
 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 

Inrush Power: 350VA 

 

Steady state : 50VA

 

 
Use  the  following  procedure  to  install  the 
Command  Closing  Coil  accessory  into  the  circuit 
breaker. 
 
1. Verify that the rating on the Command Closing 
Coil  identification  plate  matches  the  voltage 
rating  required  for  the  application,  as  listed  in 
Table 1. 
 
 
2.  Turn the breaker off and discharge the closing 
springs by depressing the OFF and ON buttons in 
the  sequence  OFF-ON-OFF.    Verify  that  the 
breaker OFF-ON indicator shows OFF on a green 
background and that the charge indicator shows 
DISCHARGE  on  a  white  background.    If  installing 
in a draw-out type breaker remove breaker from 
adaptor (cassette) before continuing. 
 
3.    Loosen  the  6  screws  on  front  cover  (fascia) 
using a posidrive screw driver as shown in Fig 1.B 
Rotate  the  charging  handle  down  and  slide  the 
front  cover  over  the  handle  to  remove  the  front 
cover as shown in Fig. 1.C. 
 
 

 

DEH-41418 Installation Instructions 

EntelliGuard 

®

 G Circuit Breaker 

Accessories 
 
 

Command Closing Coil

 

WARNING: Before installing any accessories, turn the 
breaker OFF, disconnect it from all voltage sources, 
and discharge the closing spings. 

AVERTISSEMENT: Avant d’installer tout accessoire, 

mettre le disjoncteur en position OFF, le déconnecter 

de toute tension d’alimentation , et déch

arger les 

resorts d’armement

 

 

 

 

Содержание GCCC024DR

Страница 1: ...r 1 Verify that the rating on the Command Closing Coil identification plate matches the voltage rating required for the application as listed in Table 1 2 Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF ON OFF Verify that the breaker OFF ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a wh...

Страница 2: ...mbly 5 Tilt the coil forward and engage the front hooks into the mechanism top support plate as shown in the Fig 3 Figure 3 Coil Assembly 6 Tilt the device backwards until the rear hooks engage in the slots on the mechanism top support plate as shown in the Fig 4 Figure 4 Coil Assembly 7 After installing the closing coil on the mechanism top plate connect the input wire assembly plug to the A9 A10...

Страница 3: ...6 Figure 6 Close Coil wire routing Installation of Electrical close switch 10 Slide the switch assembly over the mechanism side sheet and locate in the two locating holes as shown in Fig 7 Figure 7 EC switch assembly 11 Assemble the screw with washer as shown in Fig 8 Tighten the screw to torque 2Nm 1 47ft lbs Figure 8 Screw assembly 12 Plug the connector from the EC switch assembly to the connect...

Страница 4: ...with the screw washer as shown in fig 11 Fig 11 Push button assembly 15 Rotate the charging handle down and slide the front cover over the handle to assemble the front cover to housing as shown in Fig 12 Figure 12 16 Ensure the fascia is aligned properly with the trip unit and the pad lock features of the breaker 17 Fasten the 6 mounting screws of fascia with the housing using a pozidrive screwdri...

Страница 5: ...ce Command Closing Coil Connection Scheme A10 provides constant control power to the Command Close Coil accessory A9 control power return A11 Separate local command input Must be fed from the same source as A10 ...

Страница 6: ...Function Code 05 ON to register 111 The command will remain in effect until it is turned OFF To turn off the command send a COIL OFF command Modbus Function Code 05 OFF to register 111 Note that the remote command input must be set to OFF and the local command inputs must be OFF before the close coil can be retriggered with a new command Refer to DEH 4567 EntelliGuard Trip Unit Instruction for mor...

Отзывы: