background image

 

Installation of Push button on the fascia: 
 

13. Remove the existing dummy button by 
removing the screw as shown in fig 10. 
 

 

 

Figure 10. Connector plug assembly 

 
 
14. Insert the push button and the spring from the 
front of the fascia. Assemble them to the fascia 
with the screw & washer as shown in fig 11. 

 

 

 

 

 

 

 

Fig 11.  Push button assembly

 

 

 

 

 
15

. Rotate the charging handle down and slide 

the front cover over the handle to assemble the 
front cover to housing as shown in Fig. 12. 
 

 

 

                                     Figure 12.

 

 
16. Ensure the fascia is aligned properly with the  
trip unit and the pad lock features of the breaker. 
 
 
17. Fasten the 6 mounting screws of fascia with 
the housing using a pozidrive screwdriver.  Apply 
torque of 6 Nm (4.42ft-lbs). 
 
 
 
 
 
 
 

                   

 

                                 

 

                                

 

 
 
 

 
 
 

Dummy button 
Screw 

Содержание GCCC024DR

Страница 1: ...r 1 Verify that the rating on the Command Closing Coil identification plate matches the voltage rating required for the application as listed in Table 1 2 Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF ON OFF Verify that the breaker OFF ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a wh...

Страница 2: ...mbly 5 Tilt the coil forward and engage the front hooks into the mechanism top support plate as shown in the Fig 3 Figure 3 Coil Assembly 6 Tilt the device backwards until the rear hooks engage in the slots on the mechanism top support plate as shown in the Fig 4 Figure 4 Coil Assembly 7 After installing the closing coil on the mechanism top plate connect the input wire assembly plug to the A9 A10...

Страница 3: ...6 Figure 6 Close Coil wire routing Installation of Electrical close switch 10 Slide the switch assembly over the mechanism side sheet and locate in the two locating holes as shown in Fig 7 Figure 7 EC switch assembly 11 Assemble the screw with washer as shown in Fig 8 Tighten the screw to torque 2Nm 1 47ft lbs Figure 8 Screw assembly 12 Plug the connector from the EC switch assembly to the connect...

Страница 4: ...with the screw washer as shown in fig 11 Fig 11 Push button assembly 15 Rotate the charging handle down and slide the front cover over the handle to assemble the front cover to housing as shown in Fig 12 Figure 12 16 Ensure the fascia is aligned properly with the trip unit and the pad lock features of the breaker 17 Fasten the 6 mounting screws of fascia with the housing using a pozidrive screwdri...

Страница 5: ...ce Command Closing Coil Connection Scheme A10 provides constant control power to the Command Close Coil accessory A9 control power return A11 Separate local command input Must be fed from the same source as A10 ...

Страница 6: ...Function Code 05 ON to register 111 The command will remain in effect until it is turned OFF To turn off the command send a COIL OFF command Modbus Function Code 05 OFF to register 111 Note that the remote command input must be set to OFF and the local command inputs must be OFF before the close coil can be retriggered with a new command Refer to DEH 4567 EntelliGuard Trip Unit Instruction for mor...