Transmit logic
GUID-0CFA8B44-2841-4ADF-AB6D-891A6E04C55B v1
The task of the transmit logic is to boost (Com Boost) the PLC transmitter and transmit a
signal (signaling relay output Com Send) [HFSEND] to the opposite end of the line (signaling
relay output Com Boost) [HFBOOST].
General rules are:
•
The underreaching zone transmits the signal in a permissive underreaching transfer
tripping scheme (PUTT).
•
The overreaching zone transmits the signal in a permissive overreaching transfer tripping
scheme (POTT).
•
The reverse measuring zone transmits the blocking signal in an overreaching blocking
scheme (BLOCK OR).
OR
OR
OR
AND
OR
AND
AND
PUTT_ON
POTT_ON
BLOCK_ON
PUTT_SEND
POTT_SEND
BLOCK_SEND
UWEAK_L1
UWEAK_L2
UWEAK_L3
2000
START_L1L2L3
DISTBL
BIT_HF_ON
HF_SEND
HF_BOOST
18000032-IEC19000437-1-en.vsdx
IEC19000437 V1 EN-US
Figure 33: TRANSBL segment
Table 63: Signals TRANSBL
Signal
In
Out
Source
Drain
PUTT_ON
X
PUTT logic
POTT_ON
X
POTT logic
BLOCK_ON
X
BLOCK logic
PUTT_SEND
X
PUTT logic
POTT_SEND
X
POTT logic
BLOCK_SEND
X
BLOCK logic
DISTBL
X
Enabling logic SUPBL
UWEAK_L1
X
UL1 < Umin
UWEAK_L2
X
UL2 < Umin
UWEAK_L3
X
UL3 < Umin
START_L1L2T
X
Binary output: Start L1+L2+L3
Table continues on next page
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
83
Technical manual