5.4
Directional overcurrent definite time protection 67
(DIROCDT)
5.4.1
Mode of operation
GUID-65CB2975-ADFB-4D2B-8923-3A0C57A02EB7 v1
Directional overcurrent function:
•
detecting phase faults on ring lines
•
detecting phase faults on double-circuit lines with an infeed at one end
•
backup protection for a distance protection scheme
5.4.2
Features
GUID-0502CD95-362C-4826-9B26-32533106C57C v1
•
Directional phase fault protection
•
Insensitive to DC component
•
Insensitive to harmonics
•
Voltage memory feature for close faults
5.4.3
Inputs and outputs
5.4.3.1
CT/VT inputs
GUID-B92FE713-87AB-48C5-B7E3-B2C694BEF819 v1
•
Current
•
Voltage
5.4.3.2
Binary inputs
GUID-35EB42DC-C990-4FAD-A2BB-F917C4FD096A v1
•
Blocking
•
PLC receive
5.4.3.3
Binary outputs
GUID-4742C8ED-8E75-406E-8618-E7BF2947A0F1 v1
•
Start
•
Start L1
•
Start L2
•
Start L3
•
Forwards measurement
•
Backwards measurement
•
Tripping
5.4.3.4
Measurements
GUID-67F086A8-8A33-44FD-AC5C-097F44217914 v1
•
Current amplitude of the three phase currents (IL1, IL2, IL3)
•
Active power
•
A positive measurement indicates the forwards direction (IL1 × UL2L3, IS × UL3L1, IL3 ×
UL1L2)
•
Voltage amplitude of the phase-to-phase voltages (UL2L3, UL3L1, UL1L2)
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
99
Technical manual