5.1.5
Parameters
GUID-94E19491-6E52-44C9-813E-33C133EF4CC3 v1
Table 42: General
Parameter
Description
ParSet 1..4
Parameter for determining in which set of parameters a particular function is active.
CT Neutral
Side of the CTs on which the star-point is formed (current direction).
Choice:
•
Bus side
•
Line side
Ref. Length
Reactance (secondary value) to be used as reference length of the line.
U input
Indicates the first VT input assigned to the three-phase voltages. Fixed setting
Channel 5 of the A/D module.
I input
Indicates the first CT input assigned to the three-phase currents. Fixed setting
Channel 1 of the A/D module.
I
0
input,
I
0P
input
Indicates the CT input assigned to the neutral current. This is used for
•
the external acquisition of the neutral current of the line or
•
the neutral current of the parallel circuit of a double-circuit line. Fixed setting
Channel 4 of the analogue input module.
I O/C backup
Phase current pick-up setting of the backup overcurrent unit. The function is
blocked when set to zero.
Delay O/C backup
Tripping delay of the O/C backup function.
Time PS block
Determines the maximum blocking time of the power swing blocking function. The
power swing blocking function is blocked when set to zero.
Table 43: Starting
Text
Explanation
StartMode
Choice:
•
UZ (underimpedance)
•
I > (overcurrent)
PhaseSelMode
Phase preference for cross-country faults in systems with Petersen coils and
ungrounded systems:
Choice:
•
Solidly grounded
•
L1L3L2 (L1) cyclic
•
L3L1L2 (L3) cyclic
•
L1L3L2 acyclic
•
L1L2L3 acyclic
•
L3L2L1 acyclic
•
L3L1L2 acyclic
•
L2L1L3 acyclic
•
L2L3L1 acyclic
•
Directional OR
GndFaultMode
Method of detecting ground faults:
Choice:
•
I
0
: (I
E
>3I
0min
) AND (I
E
>0.25 I
max
)
•
I
0
OR U
0
: (I
E
>3I
0min
) AND (I
E
>0.25 I
max
) OR (U
E
>3U
0min
)
•
I
0
(I
2
): (I
E
>3I
0min
) AND (I
E
>0.23 I
2
)
•
I
0
(I
2
) OR U
0
: (I
E
>3I
0min
) AND (I
E
>0.23 I
2
) OR (U
E
>3U
0min
)
Table continues on next page
Section 5
1MRK 505 406-UEN B
Bay protection functions
30
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved