c = 0.02
:
normal inverse
c = 1
:
very inverse and long time earth fault
c = 2
:
extremely inverse
•
Insensitive to DC component
•
Insensitive to harmonics
•
Voltage memory feature for close faults
5.5.3
Inputs and outputs
5.5.3.1
CT/VT inputs
GUID-BF590066-EAD6-44A1-93E8-312890FCE7E0 v1
•
Current
•
Voltage
5.5.3.2
Binary inputs
GUID-BD06D555-60CE-4A51-9077-81CE1142256E v1
•
Blocking
•
PLC receive
5.5.3.3
Binary outputs
GUID-C59C9A87-BD2E-4EE1-9A71-847ADC642458 v1
•
Start
•
Start L1
•
Start L2
•
Start L3
•
Forwards measurement
•
Backwards measurement
•
Tripping
5.5.3.4
Measurements
GUID-D59AA2D3-FAEF-4F61-B7A1-1C8C6BA71BB7 v1
•
Current amplitude
Amplitude of the three-phase currents (I
L1
, I
L2
, I
L3
)
•
Active power
A positive measurement indicates the forwards direction (I
L1
× U
L2L3
, I
L2
× UL3
L1
, I
L3
× U
L1L2
)
•
Voltage amplitude
Amplitudes of the phase-to-phase voltages (U
L2L3
, U
L3L1
, U
L1L2
)
5.5.4
Function settings
GUID-E0DE2E94-EF62-4944-AE37-55CC917D3A30 v1
Table 75: Directional overcurrent inverse time function - settings
Text
Unit
Default
Min
Max
Step
ParSet4..1
P1
(Select)
CurrentInp
CT/VT-Addr
CT I1-I3
VoltageInp
CT/VT-Addr
VT U1-U3
I-Setting
IN
2.00
0.20
20.00
0.01
Angle
Deg
45
-180
+180
15
Table continues on next page
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
105
Technical manual
© Copyright 2019 ABB. All rights reserved