Table 58: Signals PUTT_REC (see above diagram)
Signal
In
Out
Source
Drain
PUTT_NONDIR
PUTT_FWD
PUTT_OR
X
Setting: Com Mode
PUTT non-directional:
PUTT_NONDIR = 1
PUTT Forwards:
PUTT_FWD = 1
PUTT OR2:
PUTT_BWD = 1
DELAY2
X
Binary output: Delay 2
M_OWN
X
Internal logic signal (TRIP2)
START_L1L2L3
X
Binary output: Start L1+L2+L3
UZ_FWD
X
Binary output: Meas Fward
MEAS OR2
X
Binary output: Meas Oreach
BIT_UNBL
X
Internal logic signal (UNBLOCK)
HFREC
X
Binary input: Com Rec
P_WEAK
X
Setting: Weak
On = 1; Off = 0
UWEAK_L1
X
UL1 < Umin
UWEAK_L2
X
UL2 < Umin
UWEAK_L3
X
UL3 < Umin
TRIP_PUTT
X
Internal signal to
tripping logic (TRIP2),
where it is compared
with all the tripping
conditions to generate
the binary signals Trip
L1, Trip L2 etc.
UWEAK_PUTT
X
Internal signal to
tripping logic (TRIP1)
UWEAK_L1_PUTT
X
Internal signal to
tripping logic (TRIP1)
UWEAK_L2_PUTT
X
Internal signal to
tripping logic (TRIP1)
UWEAK_L3_PUTT
X
Internal signal to
tripping logic (TRIP1)
Permissive overreaching transfer tripping (POTT)
GUID-0BCB973B-50BB-4274-B7A5-6E26D6CDC88D v1
The POTT logic is divided into a receive logic (POTT_REC) and a transmit logic (POTT_SEND).
The receive logic (POTT_REC) transfers its output signals to the tripping logic. Account is
taken of any weak infeed (Weak) [UWEAK_L1, L2, L3], a short enable signal in the event of
failure of the communication channel (Unblock) [BIT_UNBL] or transient blocking (Transbl)
[BIT_TBE] signal.
The logic (POTT_SEND) transfers its output signals to a com-mon transmit logic for PUTT,
POTT and BLOCK OR schemes, while taking account of any echo signal received in the event of
a weak infeed. The criteria for tripping [TRIP_POTT] and transmission [SEND_POTT] of a
transfer trip signal by the distance protection function in a POTT scheme are given in the
tabular overview below:
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
75
Technical manual
© Copyright 2019 ABB. All rights reserved