Underimpedance starters (UZ) up to initial pick-up
GUID-69036925-0AA6-488C-A93E-410F5C113C09 v1
The variables at the inputs of the underimpedance starters are the phase currents I
L1
, I
L2
and
I
L3
and the residual current I
E
(3I
0
) and the phase-to-neutral voltages U
L1
, U
L2
, U
L3
and the
neutral voltage U
E
(3U
0
).
U
L1
, U
L2
, U
L3
, U
E
,
I
L1
, I
L2
, I
L3
, I
E
START
(I
E
> 3I0min) AND
(I
E
>0.25Imax) AND/OR
(U
E
>3U0min)
(Iph > Imin
UPh
Z = -----------
2 x IPh
Z < Z Start
Set temp.
signals “Ph”,
“E”
All Ph-0
loops
Loop =
Phase selection
Uph Uph1 – Uph2
Z = ------------------- or Z = -------------------
1x Iph + 1 x IE Iph1 – Iph2
Z < ZStart
Log.signals =
temp.signals
END
Y
Y
N
Y
N
Y
N
Y
N
(Iph1 > Imin)
AND
(Iph2 > Imin
Uph1 – Uph2
Z = ---------------------
Iph1 – Iph2
Z < Z Start
Set temp.
signals “Ph1”,
“Ph2”
All Ph-Ph
loops
Selectivity
conditions
Set
log. signals
N
Y
J
N
Y
18000013-IEC19000415-1-en.vsdx
IEC19000415 V1 EN-US
Figure 14: Underimpedance starters (UZ)
Depending on the setting of the parameter
Gnd Fault Mode (I
0
, I
0
AND U
0
, I
0
OR U
0
), the
function determines initially whether one or both of the ground fault criteria are fulfilled, that
is, whether the residual current I
E
exceeds the setting of the parameter
3I0min and/or the
residual voltage U
E
the setting of the parameter
3U0min. Should this be the case, the three
phase-to-ground loops are measured first, otherwise just the three phase-to-phase loops.
The three phase-to-ground loops are processed as follows:
If I
L1
(or I
L2
, or I
L3
) is greater than I
min
, the corresponding loops are enabled and the loop
impedances calculated as follows:
Section 5
1MRK 505 406-UEN B
Bay protection functions
54
Bay protection functions REB500
Technical manual