autoreclosure (200 ms) or not (10 s). For dead times longer than 10 s (autoreclosure function)
there is the possibility of using the blocking input Ext Blk SOTF. This is a binary input which is
interlocked by [P_SOTF_INIT] via an AND gate.
Combining undervoltage and a missing current enable signal [CREL_L1, L2, L3] as in alternative
3) prevents mal-operation of the logic after 200 ms, respectively 10 s, in cases of system faults
with low fault current contribution detected in the higher distance zones.
Resetting of the signal SOTF [START_SOTF] is delayed by 1 s, that is, every distance protection
start within a time of 1 s after one of the three switch-onto-fault criteria was fulfilled gives rise
to three-phase tripping [SOTF] of the circuit-breaker.
Uweak_L1
Uweak_L2
Uweak_L3T
AND
CREL_L1
CREL_L2
OR
DeadLine
AND
SOTF_10S
AND
10000
200
OR
1000
AND
MANCL_DIST
SO TF_INI
START_SO TF
SO TF
CREL_L3
18000020-IEC19000422-1-en.vsdx
18000020-IEC19000425-1-en.vsdx
IEC19000422 V1 EN-US
Figure 21: SOFT segment
Table 53: Signals SOFT (see above diagram)
Signal
In
Out
Source
Drain
Uweak_L1
X
Starter: UL1 < Umin
Uweak_L2
X
Starter: UL2 < Umin
Uweak_L3
X
Starter: UL3 < Umin
CREL_L1
X
Starter: IL1 > Imin (current release)
CREL_L2
X
Starter: IL2 > Imin (current release)
CREL_L3
X
Starter: IL3 > Imin (current release)
DeadLine
X
Binary input: DeadLine
SOTF_10S
X
Setting: SOFT 10sec
(On=1 / Off=0)
MANCL_DIST
X
Binary input: Manual Close
Table continues on next page
Section 5
1MRK 505 406-UEN B
Bay protection functions
70
Bay protection functions REB500
Technical manual