The logic solves the following problem (see
t = 0 s :
t = sign.rec.:
t = CB open :
Relays A1, B1 and B2
detect the fault in
the OR zone and
send a signal to the
Remote end. Relay
A2 detects a
backward fault.
A1
A2
B2
B1
A1
A2
B2
B1
Relays A1, B1 and A2
receive a signal from
the Remote end.
A1
A2
B2
B1
CB A1 opens before
CB B1 opens. Relay A2
detects the fault in
the OR zone, but still
receives a signal from
the remote end, for
example, it trips and
opens the “Healthy”
line.
18000030-IEC19000435-1-en.vsdx
IEC19000435 V1 EN-US
Figure 31: Reversal of power direction
The operation of the logic is as follows (POTT solution):
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
81
Technical manual