I
Start
Pick-up setting of the overcurrent starters (only effective providing starting mode
set to I>)
I
min
Setting of the low current check feature for enabling the protection.
3I
0min
Neutral current (3I
0
) setting for detecting ground faults.
3U
0min
Neutral voltage (3U
0
) setting for detecting ground faults.
XA
Reactive reach of the impedance characteristic in the tripping direction.
XB
Reactive reach of the impedance characteristic in the restraint direction.
RA
Resistive reach of the impedance characteristic in the tripping direction.
RB
Resistive reach of the impedance characteristic in the restraint direction.
RLoad
Resistive reach for avoiding load encroachment.
AngleLoad
Limit phase-angle for avoiding load encroachment.
Uweak
Phase-to-neutral setting for detecting a weak infeed or a dead line for enabling
manually energizing the line. The function is blocked when set to zero.
18000001-IEC19000403-1-en.vsdx
X
R
27°
27°
XA
- XB
RA
- RB
RLoad
- RLoad
Directional
(tripping direction)
Load angle
Direc-
tional
OR
IEC19000403 V1 EN-US
Figure 2:
Underimpedance starter settings
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
31
Technical manual