BP internal signal
Designation of binary output
signal
Description
Trip L1L2L3
Trip L1L2L3 Aux
211310_DIST Trip L1L2L3
211315_DIST Trip L1L2L3 Aux
General tripping signal. This signal is not
disabled while a blocking signal is being
applied.
Trip CB 3P
211320_DIST Trip CB 3ph
Three-phase trip signal. This signal is
disabled while a blocking signal is being
applied with the exception of a trip by the
backup overcurrent protection.
Trip CB 1P
211325_DIST Trip CB 1ph
Single-phase trip signal. This signal is
disabled while a blocking signal is being
applied with the exception of a trip by the
backup overcurrent protection.
Trip O/C
211330_DIST Trip O/C
Backup overcurrent trip signal.
Trip SOTF
211335_DIST Trip SOTF
Switch-onto-fault trip signal.
Trip Com
211340_DIST Trip Com
Signal for tripping either enabled by the
receipt of a permissive signal or the non-
receipt of a blocking signal. (This signal is
disabled while a blocking signal is being
applied.)
Trip Stub
211345_DIST Trip Stub
Short-zone protection trip signal.
Dist Blocked
211405_DIST Blocked
Signal indicating that the distance
protection is blocked.
DelDistBlk
211410_DIST Del Blocked
Signal delayed by 12 s indicating that the
distance protection is blocked.
Start L1+L2+L3
211705_DIST Start L1+L2+L3
General distance protection starting signal
(OR logic for all starting signals excepting
‘weak infeed').
Start L1L2L3
Start L1L2L3 Aux
211710_DIST Start
L1L2L3211715_DIST Start L1L2L3
Aux
General distance protection starting signal
(OR logic for all starting signals including
weak infeed').
Start L1
Start L1 Aux
211720_DIST Start L1
211725_DIST Start L1 Aux
Distance protection L1 phase starting signal
(including ‘weak infeed').
Start L2
Start L2 Aux
211730_DIST Start L2
211735_DIST Start L2 Aux
Distance protection L2 phase starting signal
(including ‘weak infeed').
Start L3
Start L3 Aux
211740_DIST Start L3
211745_DIST Start L3 Aux
Distance protection L3 phase starting signal
(including weak infeed).
Start L0
Start L0 Aux
211750_DIST Start E
211755_DIST Start E Aux
Distance protection E/F starting signal (U0
or I0). Only generated together with a phase
starter.
Start I0
211760_DIST Start I0
Neutral current starting signal (I0).
Start U0
211765_DIST Start U0
Neutral voltage starting signal (U0).
Start OC
211770_DIST Start O/C
Overcurrent starting signal.
Start SOFT
211780_DIST Start SOTF
Enabling signal for the switch-onto-fault
prot.
Start O/C
211785_DIST Start OC
Backup overcurrent start signal.
Start UZ
211790_DIST Start UZ
Underimpedance starting signal.
Start 1ph
211805_DIST Start 1ph
Indicates that the distance protection was
started by a single phase.
Delay >= 2
211810_DIST Delay >= 2
Signal for starting in Zone 2 or higher.
Delay 1
211815_DIST Delay 1
Signal for starting in Zone 1.
Delay 2
211820_DIST Delay 2
Signal for starting in Zone 2.
Delay 3
211825_DIST Delay 3
Signal for starting in Zone 3.
Table continues on next page