Figure 50: Distance protection and autoreclosure functions in different units
5.8.6.3
Connections between autoreclosure and overcurrent functions
GUID-A6CF8718-6382-4229-8E4E-88F3788A1298 v1
To prevent the discrimination timer from operating, connect the overcurrent Trip signal to the
two inputs Start and Trip CB 3P of the autoreclosure function.
The time
t Close must be set longer than the maximum operating time of the activated
(graded) overcurrent functions:
t
Close from AR function
> t
max. overcurrent time delay
In cases where the zone extension signal is used in conjunction with overcurrent functions, the
terms ‘overreach’ and ‘underreach’ have the following meanings:
•
overreach: enabling of an overcurrent function having a short (non-graded) time delay.
•
underreach: enabling of an overcurrent function having a long (graded) time delay.
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
139
Technical manual