Table 88: Autoreclosure function - parameters
Signal
Description
ParSet 4..1
Parameter for determining in which set of parameters a particular function is active.
1. AR Mode
•
1. 1P-1P —single-phase trip and reclosure for ground faults (single-phase dead
time), no reclosure for phase faults
•
1. 1P-3P —single-phase trip followed by three phase trip after approx. 20 ms,
three-phase reclosure for ground faults (three-phase dead time initiated by
single-phase trip), no reclosure for phase faults
•
1. 1P3P-3P —three-phase trip and reclosure for earth and phase faults(three-
phase dead time)
•
1. 1P3P-1P3P —single-phase trip and reclosure for ground faults (single-phase
dead time), three-phase trip and reclosure for phase faults (three-phase dead
time)
•
Ext. Wahl —External selection by the binary inputs
MD1_EXT_1P_1P, MD1_EXT_1P_3P, MD1_EXT_1P3P_3P and MD1_EX_1P3P_1P3P
2…4AR Mode
Maximum number of reclosure attempts (all three-phase)
•
off —no 2nd, 3rd or 4th reclosure
•
2 AR —2 reclosures
•
3 AR —3 reclosures
•
4 AR —4 reclosures
t Dead1 1P
Dead time for first single-phase reclosure
t Dead1 3P
Dead time for first three-phase reclosure
t Dead1 Ext.
Extension of 1st dead time for single or three-phase reclosure Effective as long as a
logical 1 (pulse or continuous) is applied to the Extend t1 I/P before the dead time
finishes (falling edge).
t Dead2
2nd dead time
t Dead3
3rd dead time
t Dead4
4th dead time
Table continues on next page