BP internal signal
Designation of binary input signal
Description
Trip CB3 *)
118330_AR Trip CB3
Redundant general trip
CB Ready
118505_AR CB Ready
CB ready for open/close/open cycle
CO Ready
118510_AR CO Ready
CB ready for close/open cycle
CB Open
118515_AR CB Open
CB Open
CB2 Ready **)
118520_AR CB2 Ready
CB ready for open/close/open cycle
CO2 Ready **)
118525_AR CO Ready 2
CB ready for close/open cycle
CB2 Open **)
118530_AR CB2 Open
CB2 Open
Manual Close
118535_AR Manual Close
Blocking I/P excited by the manual CB close
signal.
CB2 Priority **)
118540_AR CB2 Priority
CB2 preferred circuit-breaker
Start
118705_AR Start
Start
Start 2 *)
118710_AR Start 2
Redundand start
Start 3 *)
118715_AR Start 3
Redundant start
Dead Line
118805_AR Dead Line
Deadline
Dead Line 2 **)
118810_AR Dead Line 2
Deadline 2
Extended t1
118815_AR Extended t1
External extension of dead time
Synchro Check
118820_AR Synchro Check
Synchrocheck
Synchro Check 2 **)
118825_AR Synchro Check 2
Synchrocheck 2
Ex SC ByPass
118830_AR Ext. SC ByPass
External Synchrocheck bypass
MD1_EXT_1P_1P
118835_AR EXT_1P_1P
External 1P-1P selector for 1st. AR
MD1_EXT_1P_3P
118840_AR EXT_1P_3P
External 1P-3P selector for 1st. AR
MD1_EXT_1P3P_3P
118845_AR EXT_1P3P_3P
External 1P3P-3P selector for 1st. AR
MD1_EXT_1P3P_1P3P
118850_AR EXT_1P3P_1P3P
Ext. 1P3P-1P3P select. for 1st. AR
Master Delay
118855_AR Master Delay
Delay from master CB
*) 2 and 3 denote the inputs of protection functions 2 and 3 or relays 2 and 3 in a redundant protection scheme.
**) 2 denotes the inputs for CB2 in a duplex scheme.
Table 15: BU_ DIREFGND input signals
BP internal signal
Designation of binary input signal Description
Block
120205_DIREFGND Block
Input for blocking of DIREFGND
CB Closed
120505_DIREFGND CB Closed
CB position indicator signal
Extern Start L1
120710_DIREFGND Ext. Start L1
Input for Dist. protection phase L1 starting
Extern Start L2
120715_DIREFGND Ext. Start L2
Input for Dist. protection phase L2 starting
Extern Start L3
120720_DIREFGND Ext. Start L3
Input for Dist. protection phase L3 starting
Extern Trip 3P
120725_DIREFGND Ext. Trip 3P
Input for Dist. protection Trip CB three phase
Extern Trip
120730_DIREFGND Ext. Trip
Input for Dist. protection Trip CB
Receive
120805_DIREFGND Receive
PLC receive signal
VT supervision
120810_DIREFGND VT
Supervision
Input for VT supervision
Table 16: BU_ I0INV input signals
BP internal signal
Designation of binary input signal Description
Block
121205_I0INV Block
Input for blocking of I0INV
Section 3
1MRK 505 406-UEN B
Signals
16
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved