Settings made in HMI500
VT connection:
3 phases_star (mandatory setting)
Primary voltage:
220,000 V
Secondary voltage:
100 V
Scaling factor:
1.1
4.3
Scaling factor setting for bay protection
GUID-A75CBB73-281A-482A-B09A-C94D9D528700 v1
The scaling factor only applies to the voltage functions and not to distance
protection.