Signal
Description
Receive
Input for the signal from the opposite end of the line:
•
T: not used
•
xx: all binary inputs (or outputs of protection functions)
Ext Block
•
F: not blocked
•
xx: all binary inputs (or outputs of protection functions)
Trip
Tripping signal.
Start
Pick-up signal.
Start L1
L1 phase pick-up signal
Start L2
L2 phase pick-up signal
Start L3
L3 phase pick-up signal
MeasFwd
Signals measurement in the forwards direction.
MeasBwd
Signals measurement in the backwards direction.
5.4.6
Configuration
GUID-5C6F55A5-DC42-47E0-AA26-B7C71F60D35A v1
The following parameters have to be set:
•
Pick-up current I-Setting
•
Characteristic angle Angle
•
Delay Delay
•
Time allowed for receipt of signal t
Wait
•
Response at the end of the memorized power direction time MemDirMode
•
Time during which the memorized direction is valid MemDuration
Pick-up value I-Setting
I-Setting must be selected high enough to prevent false tripping or alarms from taking place
and low enough to reliably detect the minimum fault current. The setting must be more than
the maximum transient load current and allow for:
•
CT and relay inaccuracies
•
the reset ratio
The maximum transient load current has to be determined according to the power system
operating conditions and take account of switching operations and load surges.
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
101
Technical manual