Busbar voltage — single-phase voltage measurement
•
Line voltage — single or three-phase voltage measurement
Evaluation of instantaneous values (non-digitally filtered analogue signals) resulting in a
large permissible frequency range. Detection of the largest and smallest of the three-
phase voltages in the case of three-phase measurement.
No filtering of harmonics or DC component.
•
Choice of phase for the voltage inputs on busbar and line sides (for amplitude and phase-
angle adjustment).
•
Additional voltage input (for use in double busbar stations) with provision for remote
switchover.
•
Provision for remote selecting the operating mode.
5.7.3
Inputs and outputs
5.7.3.1
CT/VT inputs
GUID-B6579214-65E0-4A16-8A18-2349524AA637 v1
•
Voltages (2 or 3 single or three-phase inputs) for:
•
uBusInput1, uBusInput2 — single-phase
•
uLineInput — single or three-phase
5.7.3.2
Binary inputs
GUID-15699343-8DDD-4FB4-A0A1-7DD8B563FD8F v1
•
2 inputs for enabling the synchrocheck function (ReleaseInp1 and ReleaseInp2)
•
3 inputs for interlocking the synchrocheck O/Ps (BlckTrigBus1, BlckTrigBus2 and
BlckTrigLine)
•
1 input for bypassing the synchrocheck function (OverridSync)
•
2 inputs for remotely selecting operating mode (OpModeInp1 and OpModeInp2)
•
2 inputs for remotely switching voltage channels in double busbar stations (uBus1Activ
and uBus2Activ)
5.7.3.3
Binary outputs
GUID-83C56EC6-18F3-47A2-B316-731024859B8B v1
•
Function pick-up (Start)
•
Circuit-breaker closing enable signal (PermitToClos)
•
Function disabled signal (SyncBlockd)
•
Enable output blocked signal (TrigBlockd)
•
Synchrocheck bypassed signal (OverridSync)
•
Amplitude difference in permissible range (AmplDifOK)
•
Phase-shift in permissible range (PhaseDifOK)
•
Frequency difference in permissible range (FreqDifOK)
•
Busbars energized (LiveBus)
•
Busbars de-energized (DeadBus)
•
Line energized (LiveLine)
•
Line de-energized (DeadLine)