Table 45: VT supervision
Text
Explanation
VTSupBlkMode
off:
Function disabled
ZeroSeq:
0
0
U
I
NegSeq:
2
2
U
I
Zero × NegSeq:
0
0
2
2
U
I
U
I
Special:
2
0
2
U
I
I
VTSupBlkDel
Delayed blocking of the distance function (12 s) for operation of the VT
supervision.
•
off immediate blocking
•
on delayed blocking
VTSupDebDel
Delay (1 s) for resetting blocking by the VT supervision.
•
off immediate reset
•
on delayed reset
U0min VTSup
Pick-up setting of the neutral voltage (U0) for VT supervision referred to the
rated VT voltage 100/√3 or 200/√3.
U2min VTSup
Pick-up setting of the negative sequence voltage (U2) for VT supervision
referred to the rated VT voltage 100/√3 or 200/√3.
I0min VTSup
Pick-up setting of the neutral current (I0) for VT supervision.
I2min VTSup
Pick-up setting of the NPS current (I2) for VT supervision.
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
35
Technical manual