The transmission criteria are fulfilled when the local measuring unit trips, the
starters have picked up and the third time step has not started.
PUTT receive logic (PUTT_REC)
GUID-DF78E9B4-5AED-4F54-BDB4-282C1DCFC704 v1
The receive logic (PUTT_REC) transfers its output signals to the tripping logic. Account is
taken of a weak infeed (Weak) [UWEAK_L1, L2, L3] or a short enable signal in the event of
failure of the communication channel (Unblock) [BIT_UNBL].
Provision is made for applying the tripping criterion to the entire underimpedance starting
characteristic (PUTT non-directional) [PUTT_NONDIR], starting in forwards direction (PUTT
Forwards) [PUTT_FWD] or the overreaching of 2nd zone (PUTT OR2) [PUTT_OR2].
AND
AND
OR
AND
OR
OR
AND
AND
AND
OR
OR
OR
PUTT_NONDIR
START_L1L2L3
PUTT_OR
MEAS_OR2
PUTT_FWD
UZ_FWD
DELAY2
M_OWN
BI T_UNBL
HFREC
P_WEAK
100
100
AND
AND
TRIP_PUTT
UWEAK_PUTT
UWEAK_L1_PUTT
UWEAK_L2_PUTT
UWEAK_L3_PUTT
UWEAK_L1
UWEAK_L2
UWEAK_L3
5000
18000025-IEC19000428-1-en.vsdx
IEC19000428 V1 EN-US
Figure 26: PUTT_REC segment