This corresponds to about 2.7 times the line reactance.
An alternative way is to set
Z2
according to:
Z2
≥
Z1
A-B
+ 0.85 ·
Z
set
(B-C)
= 17.5 + 0.85 · 10 = 26.0
Ω
If remote back–up protection is used in the network it is desirable to maximize reach
of zone 2.
If local back-up protection is used it is better to minimize the zone 2 reach.
The settings can be chosen:
,
2
2.5
2.5 2.5
17.5
44.2
Line posseq
Z
Z
j
=
×
=
×
+
=
W
GUID-60425379-F1D0-4370-8F6D-37874DE5BBBA V1 EN
(Equation 12)
4.
Set
RFPP2
to
44.00 Ω
, if
CharPPZ2
is set to
Quadrilateral
.
It is assumed that the fault resistance is equal to the fault resistances calculated for
zone 1. At a fault on an adjacent line also the fault resistance is influenced by the fault
current infeed from the other lines connected to B. The apparent value of the fault
resistance at A can approximately be calculated as:
1
3 2 8 17 5
2
17 9
3 2
source,B
source,A
A B
B C
f
f
A B
source,B
X
X
X
I
RFPP R
R
I
X
.
.
.
.
-
-
-
+
+
=
×
=
×
=
+ +
= ×
=
W
GUID-B39F72C7-DDED-495F-9DD4-55CA75A1EB0F V1 EN
(Equation 13)
This is the minimum value for the fault resistance reach
RFPP2
setting. It can be
valuable to have much higher
RFPP
setting.
RFPP2
≈
Z2
setting is proposed:
5.
Set
RFPG2
to
100 Ω
, if
CharPGZ2
is set to
Quadrilateral
.
,
,
,
1
3.2 8 17.5
11.1
99.6
3.2
source B
source A
A B
B C
f
f
A B
source B
X
X
X
I
RFPE
R
R
I
X
-
-
-
+
+
=
×
=
×
=
+ +
=
×
=
W
GUID-9D945B7C-AC4C-4C4A-92A3-503D283000BA V1 EN
(Equation 14)
This is the minimum value for the fault resistance reach
RPG2
setting. It can be
valuable to have much higher
RFPG2
setting.
RFPG2
≈ 2.3 · Z2 setting is proposed
(should never be larger than 4.5 · X2 where X2 is the reactive part of Z2):
6.
Set
OpModetPGZ2
to
Enabled
.
Section 3
1MRK 506 334-UUS A
REL650 setting examples
52
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...