14.4.4.1
Measurement function application for a 380kV OHL
Single line diagram for this application is given in figure
380kV Busbar
380kV OHL
P
Q
800/5 A
ANSI09000039-1-en.vsd
380kV 120V
/
3 3
kV
IED
ANSI09000039 V1 EN
Figure 209:
Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in
figure
it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef
(see
settings for analog input modules in PCM600) using PCM600 for analog input
channels
2. Connect, in PCM600, measurement function to three-phase CT and VT inputs
3. Set under General settings parameters for the Measurement function:
•
general settings as shown in table
.
•
level supervision of active power as shown in table
.
•
calibration parameters as shown in table
.
1MRK 506 334-UUS A
Section 14
Monitoring
435
Application manual