setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1
are designated 0=FALSE and 1=TRUE:
•
289_OP = 1
•
289_CL = 0
•
789_OP = 1
•
789_CL = 0
•
7189G_OP = 1
•
7189G_CL = 0
If there is no second busbar B and therefore no 289 and 2089 disconnectors, then the
interlocking for 289 and 2089 are not used. The states for 289, 2089, 2189G, BC_12,
BBTR are set to open by setting the appropriate module inputs as follows. In the functional
block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
•
289_OP = 1
•
289_CL = 0
•
2089_OP = 1
•
2089_CL = 0
•
2189G_OP = 1
•
2189G_CL = 0
•
BC_12_CL = 0
•
VP_BC_12 = 1
•
BBTR_OP = 1
•
VP_BBTR = 1
11.5.8
Interlocking for breaker-and-a-half diameter BH (3)
11.5.8.1
Application
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half diameter
according to figure
1MRK 506 334-UUS A
Section 11
Control
373